Operating Instructions

Commissioning
Configuring communication
6
72 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
Modbus RTU protocol
Parameter Description
p0015 Select value 109 "Modbus RTU" during basic commissioning.
p2021 Valid Modbus RTU addresses: 1…247
Invalid Modbus RTU address: 0
p2020 Fieldbus baud rate
Baud rates from 4800 bps to 187500 bps can be set for communication.
Factory setting: 19200 bps
p2024 Modbus timing
Index 0: Maximum slave telegram processing time
Maximum response time from the slave to the master.
Index 1: Character delay time
Maximum permissible delay time between the individual characters in the
Modbus frame (Modbus standard processing time for 1.5 bytes).
Index2: Inter-telegram delay
Maximum permissible delay time between Modbus telegrams (Modbus
standard processing time for 3.5 bytes).
p2029 Fieldbus error statistics
Displays receive errors on the fieldbus interface.
p2031 Modbus parity
p2040 Process data monitoring time [ms]
Setting the time to monitor the process data received. If no process data is
received within this time, an appropriate message is output
Factory setting: 10000 ms
The setting 0 ms deactivates the monitoring function.
BACnet MS/TP
Parameter Description
p0015 Select value 110 "BACnet MSTP" during basic commissioning.
p2021 Valid BACnet addresses: 1…127
p2020 Fieldbus baud rate
6: 9600 bps (factory setting)
7: 19200 bps
8: 38400 bps
10: 76800 bps
p2024 Processing times
[0]: 0ms … 10000 ms, maximum processing time (APDU timeout)
Factory setting: 1000 ms
[1…2]: No significance for BACnet