Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
749
3 Function diagrams
3.18 Data sets
Fig. 3-175 8565 – Drive Data Sets (DDS)
- 8565 -
Function diagram
87654321
fp_8565_97_54.vsd
Data sets
G120 CU230P-2
13.03.2018 V4.7_10
Drive Data Sets (DDS)
DDS3
DDS2
DDS1
DDS0
r0837.1
r0051.1
<1>
A07530 "Drive data set does not exist"
(0)
DDS select., bit 0
p0820 [C]
(0)
DDS select., bit 1
p0821 [C]
DDS count
1 ... 4
p0180 (1)
DDS selected
r0837
r0837
DDS effective
r0051
r0051
Copy DDS, source
p0819[0] (0)
Copy DDS, start
p0819[2] (0)
Copy DDS, target
p0819[1] (1)
.0
.0
[2513.2]
A BICO interconnection to a parameter which is part of a drive data set always influences the currently effective data set.
Data sets can only be applied and cleared when p0010 = 15 is set.<2>