Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
48 List Manual, 04/2018, A5E33838102
Description: Displays the actual phase voltage.
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
Note: The values are determined from the transistor switch-on duration.
Description: Setting the commissioning and control view for various application classes.
Value: 0: Expert
1: Standard Drive Control (SDC)
2: Dynamic Drive Control (DDC)
Dependency: The parameter is preset when commissioning the system for the first time and for the factory setting, depending on
the power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
The following applies for p0096 = 1:
The motor type (p0300) synchronous or reluctance motor is not possible.
Note: When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor
data identification as well as the setting of the operating mode and parameterization of the closed-loop control must
be appropriately adapted.
Description: Setting the commissioning and control view for various application classes.
Value: 0: Expert
2: Dynamic Drive Control (DDC)
Dependency: The parameter is preset when commissioning the system for the first time and for the factory setting, depending on
the power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
Note: When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor
data identification as well as the setting of the operating mode and parameterization of the closed-loop control must
be appropriately adapted.
r0089[0...2] Actual phase voltage / U_phase act val
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_3 Unit selection: p0505 Func. diagram: 6730
Min Max Factory setting
- [V] - [V] - [V]
p0096 Application class / Appl_class
PM240 Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6019
Min Max Factory setting
0 2 0
p0096 Application class / Appl_class
PM330 Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6019
Min Max Factory setting
0 2 0