Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
198 List Manual, 04/2018, A5E33838102
Warning: An excessively high value may adversely affect normal drive operation.
Description: Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note: The Vdc_min controller is not switched back off until the DC link voltage rises above the threshold 1.05 * r1286 and
the controller output is zero.
Description: Sets the dynamic factor for the Vdc_min controller (kinetic buffering).
100% means that p1290, p1291, and p1292 (gain, integral time, and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, this can be carried out using the dynamic factor. In this case, p1290, p1291,
and p1292 are weighted with the dynamic factor p1287.
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note: The gain factor is proportional to the capacitance of the DC link.
The parameter is pre-set to a value that is optimally adapted to the capacitance of the power unit.
Description: Sets the integral time for the Vdc controller (DC link voltage controller).
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
r1286 Vdc_min controller switch-in level (kinetic buffering) (U/f) / Vdc_min on_level
PM240
PM330
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6320, 6854
Min Max Factory setting
- [V] - [V] - [V]
p1287[0...n] Vdc_min controller dynamic factor (kinetic buffering) (U/f) / Vdc_min dyn_factor
PM240
PM330
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6320, 6854
Min Max Factory setting
1 [%] 10000 [%] 100 [%]
p1290[0...n] Vdc controller proportional gain (U/f) / Vdc_ctrl Kp
PM230
PM240, PM330
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6320, 6854
Min Max Factory setting
0.00 100.00 1.00
p1291[0...n] Vdc controller integral time (U/f) / Vdc_ctrl Tn
PM230
PM240, PM330
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6320, 6854
Min Max Factory setting
0 [ms] 10000 [ms] 40 [ms]