Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
117
2 Parameters
2.2 List of parameters
Description: Setting and connector output to control the analog outputs via fieldbus.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: Refer to: p0771
Note: AO: Analog Output
The following interconnections must be established to control the analog outputs via fieldbus:
- AO 0: p0771[0] with p0791[0]
- AO 1: p0771[1] with p0791[1]
Description: Sets the simulation mode for digital inputs.
Dependency: The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
T: Terminal
Description: Sets the setpoint for the input signals in the digital input simulation mode.
p0791[0...1] CO: Fieldbus analog outputs / Fieldbus AO
CU230P-2_HVAC
CU230P-2_BT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-200.000 [%] 200.000 [%] 0.000 [%]
p0795 CU digital inputs simulation mode / CU DI simulation
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2221, 2256
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) Simulation Terminal eval -
01 DI 1 (T. 6) Simulation Terminal eval -
02 DI 2 (T. 7) Simulation Terminal eval -
03 DI 3 (T. 8) Simulation Terminal eval -
04 DI 4 (T. 16) Simulation Terminal eval -
05 DI 5 (T. 17) Simulation Terminal eval -
11 DI 11 (T. 3, 4) AI 0 Simulation Terminal eval -
12 DI 12 (T.10, 11) AI 1 Simulation Terminal eval -
p0796 CU digital inputs simulation mode setpoint / CU DI simul setp
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2221, 2256
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) High Low -
01 DI 1 (T. 6) High Low -
02 DI 2 (T. 7) High Low -
03 DI 3 (T. 8) High Low -
04 DI 4 (T. 16) High Low -
05 DI 5 (T. 17) High Low -
11 DI 11 (T. 3, 4) AI 0 High Low -
12 DI 12 (T. 10, 11) AI 1 High Low -