Operating Instructions

List of Parameters
Parameters
1-445
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Display parameter for the signal QU that output quantity Y of instance INT 0 of the integrator has reached the upper
limit value LU.
Description: Display parameter for the signal QL that output quantity Y of instance INT 0 of the integrator has reached the lower
limit value LL.
Description: Setting parameter for the run-time group in which instance INT 0 of the integrator is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance INT 0 within the run-time group set in p20264.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source of input quantity X of instance LVM 0 of the double-sided limiter.
r20262 BO: INT 0 integrator at the upper limit QU / INT 0 QU
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r20263 BO: INT 0 integrator at the lower limit QL / INT 0 QL
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
p20264 INT 0 run-time group / INT 0 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
5 9999 9999
p20265 INT 0 run sequence / INT 0 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 32000 700
p20266 CI: LVM 0 input X / LVM 0 input X
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0