Specifications
68
APPENDIX-F: APPLICATION SPECIFIC
DETECTION
Application Specific Detection (ASD) allows the system designer to program an HFP-11
detector’s sensitivity, pre-alarm threshold, and other alarm-related parameters using English
descriptions of the detector's environment (application). This eliminates the need for detailed
knowledge of smoke detector terminology and operation. The designer can set all of the critical
detector parameters by simply selecting an application description that closely fits the one
where the detector is to be installed.
For example, to use ASD to select the optimal parameters for a detector in a hotel lobby,
select the LOBBY application in the FS-CT2 tool for that device. The system will automatically
transmit the factory determined sensitivity, pre-alarm threshold, and detection algorithm (R-
algorithm) to the corresponding device. This eliminates the guesswork of selecting these
parameters for different environments.
ASD APPLICATIONS
ASD Application ASD Description
Disable No Applications (Standard Photo/thermal Detector)
Office (Retail) Reasonably clean, climate controlled atmosphere
Warehouse (Light Manufacturing) Airborne dust, equipment, fork truck and light to medium dock
area exhaust fumes
Lobby Relatively clean area, temperature changes, cellular phones,
smoking
Computer Room Very controlled environment, clean, temperature closely
regulated, high cost clean machinery operating, no smoking,
high air velocity
Dormitory Airborne dust and temperature changes, living quarters,
cooking fumes, smoking
Healthcare Higher level risk, relatively clean, electronic equipment
Parking Garage Airborne dust, car and diesel fumes, temperature swings
Utility (Transformer) Room Normal to somewhat dirty environment, heat from running
equipment
Precious Storage (Sensitive
Environment)
Sensitive materials or equipment storage, clean dust-free
environment, earliest warning desired
Hostile Environment Dirty, dusty, humid, operating equipment, RF present, wide
temperature swings
Duct (Open air or duct housing) Dirty, dusty, humid, wide temperature swings, high air velocity