Installation Instructions
P/N 315-049103C-3 
The following table shows the dip switch settings for proper addressing of the FS-RD2-C remotes. 
Address  Switch 1  Switch 2  Switch 3  Switch 4 
1  On On On On 
2  Off On On On 
3 On Off On On 
4  Off Off On On 
5 On On Off On 
6  Off On Off On 
7  On Off Off On 
8  Off Off Off On 
9  On On On Off 
10 Off On On Off 
11 On Off On Off 
12 Off Off On Off 
13 On On Off Off 
14 Off On Off Off 
15 On Off Off Off 
16 Off Off Off Off 
The following table gives the currents necessary for power supply and battery calculations. 
Input Current 
Model 
Input Voltage 
Type & 
Designation 
Normal 
Standby 
Maximum 
(Alarm) 
Frequency 
Ripple 
Voltage 
FS-RD2-C 
24 V DC  0.020 A  0.085 A  N/A  N/A 
SW-9 
OFF ON 
1 
2 
3 
4 