Installation Instructions

P/N 315-699462-8
2
FS-MT WIRING
ALARM
ALARM WITH
TROUBLE
LE1
LE2
TB2
TB1
J2
+
CA
-
+
CT
-
Local Energy Municipal Tie Connection Ratings:
Non- Power Limited
Supervised for opens only.
Voltage: 2
4VDC nominal, filtered (31VDC max)
Standby Current: 0.007A maximum
Trip Alarm Current: 0.400A maximum (Momentary pulse)
Maximum Wire Loop Resistance: 30 ohms
Trip Coil Impedance: 14.5 ohms
Reverse Polarity Municipal Tie Connections Ratings:
Non-Power Limited
Receiver must supervise wiring.
Voltage: 24VDC nominal
, filtered (31VDC max)
Current: 0.020A maximum (normal or alarm)
Current: 0.025A maximum (shorted)
Local Energy
City Box
Reverse Polarity Receiver
(Set J2 for proper operation)
Reverse Polarity Receiver
(Program for trouble and/or
supervisory operation)
Intended for connection to a polarity reversal circuit of a
remote station receiving unit having compatible ratings.