Specifications
TXL 1000
FIRE ALARM SYSTEM
ss
ss
s
CATALOGUE NUMBER
10125
Siemens Building Technologies, Ltd.
• Large system capacity
• Modular design
• Each Indicating Circuit can be configured as
Silenceable or Non-Silenceable
• Audibles may be configured as Steady, Temporal
Code, California Code or March Time
• Each Initiating Circuit can be configured as Alarm,
Supervisory, Waterflow or Trouble
• Two LEDs per Initiating circuit; one for Trouble and
one for Status
• Initiating and Indicating Circuits may be
individually disconnected by a DIP switch
• Configurable Signal Silence Inhibit, Auto Signal
Silence, Two-Stage Operation and One Man Walk
Test
• Subsequent Alarm, Supervisory and Trouble
operation
• Two outputs for 4 wire resettable smoke power
supply (200 mA Max. each)
• Auxiliary relay contacts for Common Alarm and
Common Supervisory as well as a Common
Trouble Relay (Each relay contact Form C, 28
VDC @ 1 Amp (resistive)
• RS-485 Interface for TRA-1000 Remote Multiplex
Annunciators
• Interface for Remote Trouble Indicator
• Easy configuration via push buttons and DIP
switches on the front panel
• Fully site or field programmable Indicating Circuits
and Auxiliary Relays
• Extensive Transient Protection
• Slide-in labels for zone identification
• 6 Amp or 12 Amp power supplies available
• Removable door for easy installation and servicing
• Removable terminal blocks for easy wiring and
servicing
• ULC Listed
Optional Modules
• TUDACT-100 Universal Digital Communicator
• TDACT-100 Digital Communicator
• Polarity Reversal and City Tie Module
• Two sizes of Surface mounted cabinets
• Semi-Flush mounting available with use of
optional trim rings
Standard Features
Siemens
TM
Series 1000 Microprocessor Based Fire Alarm
Control Panels are Multi-Zone units designed for maximum
flexibility and easy installation and operation. Fully
configurable from the front panel using push buttons and
DIP switches, the TXL 1000 enables the user to configure
the system to meet their specific requirements. With a large
capacity of supervised Class A (Style D) or Class B (Style
B) Initiating Circuits and supervised Class A (Style Z) or
Class B (Style Y) Indicating Circuits, the
Description
TXL 1000 is designed to meet virtually all applications.
The TXL 1000 consists of a Main Fire Alarm Chassis which
houses and controls all other modules. Additional modules
may be installed to configure the system to meet any
requirements that the user may have. The TXL 1000 allows
for additional Indicating Circuit, Initiating Circuit and Relay
modules to be added to the system. In addition it allows for
optional modules such as the TDACT-100 Digital
ENGINEERS AND ARCHITECTS SPECIFICATIONS
Fire Safety
ss
ss
s
ss
ss
s
TXL-1000
TXL-1000