Specifications

TXL-1008K
Fire Alarm Control Panel
ss
ss
s
CATALOGUE NUMBER
10121
Siemens Building Technologies, Ltd.
FEATURES
8 Class B (Style B) Initiating Circuits which may be
configured as 4 Class A (Style D) Circuits.
Expandable up to 24 Class B or 12 Class A Initiating
Circuits
4 Class A/B (Style Z/Y) Indicating Circuits with individual
trouble indicators (1.7 Amps max. per circuit)
Each Indicating Circuit can be configured as Silenceable
or Non-Silenceable. Audibles may be configured as
Steady, Temporal Code, California Code or March Time
Each Initiating Circuit can be configured as Alarm,
Supervisory, Waterflow or Trouble
Two LEDs per Initiating circuit; one for Trouble and one
for Status
Initiating and Indicating Circuits may be individually
disconnected by a DIP switch
Configurable Signal Silence Inhibit, Auto Signal Silence,
Two-Stage Operation and One Man Walk Test
Alarm Verification on Initiating Circuits
Subsequent Alarm, Supervisory and Trouble operation
Two outputs for 4 wire resettable smoke power supply
(200 mA Max. each)
Auxiliary relay contacts for Common Alarm and Common
Supervisory as well as a Common Trouble
Relay (Each relay contact Form C, 28 VDC @ 1 Amp
(resistive)
RS-485 Interface for RA-1000 Remote Multiplex
Annunciators
Interface for Remote Trouble Indicator
Easy configuration via push buttons and DIP switches on
the front panel
Extensive Transient Protection
6 Amp Power Supply
Removable door for easy installation and servicing
ULC Listed
OPTIONAL FEATURES
TDACT-100 Digital Communicator
Polarity Reversal and City Tie Module
Semi-Flush mounting available with use of optional trim
ring (TXL-1024TR)
The Siemens TXL-1008K Fire Alarm Control Panel is a
microprocessor based unit designed for maximum flexibility
and easy installation. Fully configurable from the front pa-
nel using the push buttons and DIP switches, it enables the
user to configure the system to meet their specific
requirements.
Description
The TXL-1008K consists of one TMCC-1024-6 Main
Chassis in a TBB-1024 Enclosure. The TMCC-1024-6 Main
Chassis comes complete with 8 Class B (Style B) Initiating
Circuits which may be configured as 4 Class A (Style D)
Circuits. It can be expanded up to 24 Class B or 12 Class
A circuits with the addition of the TDM-1008 Initiating Circuit
Module. In addition it comes equipped with 4 Class A/B
(Style Z/Y) Indicating circuits which are each rated at 1.7
Amps.
Fire Safety