Specifications
FS-250 Installation and Operation Manual
28
Observe the wiring order -- the bottom terminal is ground and must be wired back to the
electrical panel ground (earth) bonding point or another good ground acceptable to the
authority having jurisdiction and the electrical inspector. The neutral wire must be taken
back to the electrical panel neutral distribution bar and must not be grounded.
Dangerous voltages will be present on this terminal block and on other components
surrounding it and the transformer when the AC supply is turned on. Do not touch.
Battery Installation
WARNING
Improper battery connections or shorting battery terminals may damage the system and/or
batteries and may cause personal injuries.
Place the batteries in the space provided in the bottom of the back-box. If a larger than 12
AH battery set is required, a separate enclosure, CAB-BATT or any enclosure UL Listed for
Fire Protective Signaling Use, must be used.
The control panel uses a 24V battery set. Connect the two 12V batteries (or four 6V
batteries) in series with wire that is rated for the maximum worst-case battery current draw.
Route the battery leads to the left of the enclosure and up to the battery connector, J4. The
battery leads are not power-limited. DO NOT CONNECT BATTERIES YET.
Powering The Control Panel
Apply AC power to the control panel. The AC POWER ON LED, SYSTEM TROUBLE LED,
and the trouble buzzer should be on.
Observe polarity. Connect the B- (black) lead from the main board into the black or -
terminal of the battery set and the B+ (red) lead from the main board into the red or +
terminal of the battery set.
Optional Modules
See Appendix D for a listing of installation instructions for each optional module. Installation
Instructions are provided with each optional module. Follow these instructions for proper
installation.
When using the FS-DACT for either Remote Station or Central Station, you must set the
“DACT Pwr Fail Tmr” in the “System Parameters” tab of FS-CT2 as follows:
Remote Station 15 Hours
Central Station 6 Hours
Check System Operation
Check for proper operation of all the system functions. See Operation Instructions Section.
WIRING
Basic system wiring and detector locations must be in accordance with NFPA 72 or other
instructions from the appropriate local authority. Unit connections and limitations are as
indicated on the wiring diagram included below.
Technical Manuals Online! - http://www.tech-man.com










