Supervisory Conditions
Supervisory troubles are indicated similar to regular system troubles except that when a
supervisory trouble is cleared, the cleared condition continues to be indicated until it is
acknowledged.
Maintenance
In order to insure continued safe and reliable operation of the fire alarm system, periodic
inspection and testing should be performed in accordance with applicable NFPA 72
standards.
If the system has remote connections to the Fire Department or other monitor, be sure to
disable the remote signals and/or notify the remote monitoring station before performing
test operations.
For any required service, refer to the system manual or contact a factory authorized
representative.
ADDITIONAL OPERATING PROCEDURES
In addition to the basic fire alarm instructions above, several features are included to
facilitate maintenance and increase the versatility of the system. Following are procedures
to call up these functions.
Lamp Test
To operate the lamp test, press the MENU button. The LCD display will change to a MENU
screen. Press the button next to the “More” indication twice. Then press the button by the
“Lamp Test” indication. All lamps on the unit being operated will then light. Operating the
button next to “Esc” will then return the control panel to normal display. Note that the lamp
test operates the indicators only on the unit being operated, and no record is reported to
system history.
Drill
To activate a fire alarm drill, proceed as follows:
• Press "MENU".
• On the MENU display, select "More".
• At the next screen, select "DRILL".
• At the next screen, select "Yes".
• Operate ALARM SILENCE to terminate drill signal.