Specifications

FS-250 Installation and Operation Manual
11
Municipal Tie (Optional Municipal Tie Board FS-MT)
CA
Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation
Power limited
Supervised by receiver for short or open circuit.
Supervised by control panel for grounded circuit.
Voltage: 24 VDC nominal
Current: 0.020A maximum (normal or trouble)
Current: 0.025A maximum (shorted)
Ripple: 1.5 VAC maximum
CT
Reverse Polarity: Programmable for Trouble or Supervisory or either operation
Power limited
Supervised by receiver for short or open circuit.
Supervised by control panel for grounded circuit.
Voltage: 24 VDC nominal
Current: 0.020A maximum (normal or alarm)
Current: 0.025A maximum (shorted)
Ripple: 1.5 VAC maximum
LE
Local Energy
Not power limited
Supervised for open or grounded circuit by control panel.
Voltage: 24 VDC nominal
Standby Current: 0.007A maximum
Alarm Current: 0.400A maximum
Ripple: 1.5 VAC maximum
Maximum wire loop resistance: 30 ohms
Trip coil impedance: 14.5 ohms
DACT Circuit (Optional DACT Board FS-DACT)
Power limited
Supervised for short or open circuit
Maximum Voltage: 60 VDC
Maximum Current (shorted): 0.100 A
Additional Transformer (Optional Transformer Assembly FS-NPE)
Provides an additional 3.0 A of NAC power (max 1 per panel)
Technical Manuals Online! - http://www.tech-man.com