Specifications
FS-250 Installation and Operation Manual
11
Municipal Tie (Optional Municipal Tie Board FS-MT)
CA
• Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation
• Power limited
• Supervised by receiver for short or open circuit.
• Supervised by control panel for grounded circuit.
• Voltage: 24 VDC nominal
• Current: 0.020A maximum (normal or trouble)
• Current: 0.025A maximum (shorted)
• Ripple: 1.5 VAC maximum
CT
• Reverse Polarity: Programmable for Trouble or Supervisory or either operation
• Power limited
• Supervised by receiver for short or open circuit.
• Supervised by control panel for grounded circuit.
• Voltage: 24 VDC nominal
• Current: 0.020A maximum (normal or alarm)
• Current: 0.025A maximum (shorted)
• Ripple: 1.5 VAC maximum
LE
• Local Energy
• Not power limited
• Supervised for open or grounded circuit by control panel.
• Voltage: 24 VDC nominal
• Standby Current: 0.007A maximum
• Alarm Current: 0.400A maximum
• Ripple: 1.5 VAC maximum
• Maximum wire loop resistance: 30 ohms
• Trip coil impedance: 14.5 ohms
DACT Circuit (Optional DACT Board FS-DACT)
• Power limited
• Supervised for short or open circuit
• Maximum Voltage: 60 VDC
• Maximum Current (shorted): 0.100 A
Additional Transformer (Optional Transformer Assembly FS-NPE)
Provides an additional 3.0 A of NAC power (max 1 per panel)