Specifications
FS-250 Installation and Operation Manual 
10 
Voltage: 24 VDC nominal 
Ripple: 1.5 VAC maximum 
•  Resettable Power Output 
Power limited 
Voltage: 24 VDC nominal 
Ripple: 1.5 VAC maximum 
Status Relays 
Four relays programmable for alarm, supervisory, trouble, loss of AC. 
•  Contact Rating: 1 A, 28 VDC maximum, resistive 
•  Form C Contact 
Notification Appliance Circuits 
•  Power limited 
•  Supervised 
•  Maximum Standby Current: 3.4mA 
•  Alarm Voltage: 24 V FW nominal 
•  Maximum Ripple: 16 VAC 
•  Maximum Loop Drop Voltage: 1.0 VDC 
•  Four Style Z/Class B or two Style Y/Class A circuits 
•  Maximum NAC Current: 1.5 A / NAC circuit 
Maximum total NAC current 3.0 A (6.0 A with optional FS-NPE transformer installed) 
Serial Interface Circuit 
•  Power limited 
•  Supervised 
•  (+, -)Voltage: 24 VDC nominal 
•  (X+, X-) Voltage RS485 levels 
•  Maximum wire loop resistance: 11 ohms/line 
•  Communications: RS485 
P2 Addressable Device Circuits 
•  Power limited 
•  Supervised 
•  Voltage: 24 VDC nominal 
•  Maximum Current (shorted): 0.375A 
•  Maximum wire loop resistance: 50 ohms (see Graph on page 42) 
•  Style 4 or 6 circuit 
•  252 Addresses detectors and modules max. 
•  One Circuit 
Technical Manuals Online! - http://www.tech-man.com