Specifications

FS-250 Installation and Operation Manual
10
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Resettable Power Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Status Relays
Four relays programmable for alarm, supervisory, trouble, loss of AC.
Contact Rating: 1 A, 28 VDC maximum, resistive
Form C Contact
Notification Appliance Circuits
Power limited
Supervised
Maximum Standby Current: 3.4mA
Alarm Voltage: 24 V FW nominal
Maximum Ripple: 16 VAC
Maximum Loop Drop Voltage: 1.0 VDC
Four Style Z/Class B or two Style Y/Class A circuits
Maximum NAC Current: 1.5 A / NAC circuit
Maximum total NAC current 3.0 A (6.0 A with optional FS-NPE transformer installed)
Serial Interface Circuit
Power limited
Supervised
(+, -)Voltage: 24 VDC nominal
(X+, X-) Voltage RS485 levels
Maximum wire loop resistance: 11 ohms/line
Communications: RS485
P2 Addressable Device Circuits
Power limited
Supervised
Voltage: 24 VDC nominal
Maximum Current (shorted): 0.375A
Maximum wire loop resistance: 50 ohms (see Graph on page 42)
Style 4 or 6 circuit
252 Addresses detectors and modules max.