Brochure

Engineering
www.usa.siemens.com/hvac
G-16
Sizing and Selecting Pressure
Independent Control Valves (PICV)
Flanged
Part
Number
Line Size
Inches
(mm)
ANSI
Pressure
Class
Maximum
Flow Range
(GPM)
Close-off
Pressure
(psi)
ANSI
Leakage
Class
Pressure Independence
Range (psi)
p min p max
Normally Open*
599-07310 2-1/2 (65)
125
19 to 110
100
Class IV
(0.01%)
3.6
90
599-07315 2-1/2 (65) 26 to 154 8
599-07311 3 (80) 24 to 150 3.6
599-07316 3 (80) 31 to 190 8
599-07312 4 (100) 55 to 300 5
599-07317 4 (100) 65 to 395 10
599-07313 5 (125) 85 to 485 5
599-07318 5 (125) 105 to 595 8
599-07314 6 (150) 115 to 650 5
599-07319 6 (150) 140 to 860 9
599-07320 2-1/2 (65)
250
19 to 110 3.6
599-07325 2-1/2 (65) 26 to 154 8
599-07321 3 (80) 24 to 150 3.6
599-07326 3 (80) 31 to 190 8
599-07322 4 (100) 55 to 300 5
599-07327 4 (100) 65 to 395 10
599-07323 5 (125) 85 to 485 5
599-07328 5 (125) 105 to 595 8
599-07324 6 (150) 115 to 650 5
599-07329 6 (150) 140 to 860 9
Table Notes:
* Flanged valves are normally open but SQV spring return actuators fail open (SQV91P30U, 238 actuator prex code)
or fail closed (SQV91P40U, actuator prex code 239); SAV and SAX actuators can be wired for normally closed operation.