Project Name 230900 - 3 BAS AND CONTROL FOR HVAC
Date
3. Power: All actuators shall be 24VAC power and less than 100VA draw. Power shall be
via Class 2 wiring. Actuators requiring more than 100VA shall have a dedicated conduit
for power wiring, not mixed with the signal wiring.
4. Fail Safe: Valves actuators shall position the valve in a fail-safe position when the power
supply is disrupted or the signal goes to 0. Fail-safe according to the following
guidelines unless otherwise stated in the sequence of operations
a. Power fail safe shall be via spring loaded mechanical means
b. Any AHU hot water exposed to ventilation air shall fail open
c. AHU Chilled water coils exposed to ventilation air in possible freezing conditions
shall be fail open
d. AHU Chilled water coils that are drained in winter months or are in climate zones
without freezing conditions shall be fail-in-place
e. Terminal unit valves shall fail-in-place
f. Chiller isolation valves shall fail-in-place
g. Boiler isolation valves shall fail-in-place
h. Any steam supply serving a water heat exchanger shall fail closed
i. Any steam supply to a terminal unit coil or a coil without ventilation air shall fail
closed.
j. Any steam coil exposed to ventilation air shall fail open
5. Fail in Safe valves on primary equipment such as chilled water systems, hot water
systems and condenser water systems shall have a means to manually open the valve
when power is not available, such as a hand wheel or a geared crank with a clutch.
6. The actuator shall be designed with a current limiting motor protection. A release button
(clutch) or handle on the actuator shall be provided to allow for manual override (except
when actuator is spring return type).
7. Actuator shall provide minimum torque required for proper valve close-off. The close-
off differential pressure rating of the valve shall exceed the highest possible head
pressure available at the pump plus 10%, and still be rated for a Class IV leakage.
8. The actuator shall have the capability of adding auxiliary switches or feedback
potentiometer if specified.
9. All automatic control valves installed in locations exposed to the elements shall be
provided with weather resistant housings and heaters for climates that reach below
freezing.
10. Actuators shall be UL and CSA listed.