Basic Documentation

Table Of Contents
Project Name 230900 - 2 BAS AND CONTROL FOR HVAC
Date
d. All wiring shall comply with code requirements. Segregate high and low voltage
wiring and circuits and segregate the Fire Alarm (FACS) and BAS controls
wiring.
B. Globe Valves for Hot Water and Chilled Water Coils
1. Single-seated.
2. Fully proportioning with modulating cage trim or V-port inner valves.
3. Flow characteristics shall be modified equal percentage at approximately 30% change per
increment.
4. Rangeability shall be 100:1 or greater.
5. Body pressure rating and connection type construction shall conform to fitting and valve
schedules. The ANSI rating of the valve shall match or exceed the ANSI rating of the
piping in which the valve is installed.
6. 2” and under valves shall have a body pressure rating of ANSI class 250 or better.
Provide Female NPT connections unless other fittings are called for in the piping
drawings.
7. Valves 2-1/2” and larger valves shall have a body pressure rating of ANSI class 125 or
250 or better and connection type construction shall conform to pipe, fitting and valve
schedules for valves 2-1/2 inches or larger.
8. Minimum ANSI rating shall be ANSI 125.
9. Stainless steel stems and trim.
10. Spring loaded Teflon packing
11. Quiet in operation.
12. Fail-safe in either normally open or normally closed position in the event of power
failure.
13. Capable of operating in sequence with other valves and/or dampers when required by the
sequence of operation.
14. Capable of operating at varying rates of speed to correspond to the exact dictates of the
controller and variable load requirements.
15. Provide direct mount actuators specifically made for this valve. External valve linkages
and damper actuators are more susceptible to binding and breaking and shall not be
allowed.
16. Sizing (non Pressure Independent):
a. The valve shall be sized to have control authority over the coil branch circuit.
Valve authority shall be between 0.25 and 0.5 as defined by pressure drop at valve
full open divided by pressure drop of full circuit at design flow with valve full
open.
b. Select the control valve using the Cv of the control valve to be as close to or one
size higher than the Cv of the rest of the circuit. The Cv of the rest of the circuit
defined by the design flow of the coil (gpm) divided by the square root of the
cumulative pressure drops in the circuit, such as coil, piping, fittings, isolation
valves, balancing valves, triple duty valves, strainers, etc.
17. Water valves shall fail normally open or closed, as scheduled on plans, or as required by
sequences of operation.
C. ELECTRONIC VALVE ACTUATORS
1. Actuator shall be electric motor driving, microprocessor signal controlled.
2. Modulating valves shall be positive positioning, responding to a 0-10VDC, 2-10VDC or
4-20mA signal. Floating modulating signals are acceptable for modulation on terminal
units and radiation units. There shall be a visual valve position indicator.