Basic Documentation

Table Of Contents
Project Name 230900 - 1 BAS AND CONTROL FOR HVAC
Date
SECTION 23 09 00 – BUILDING AUTOMATION SYSTEM
This is supplemental language for a spec. This is not an all inclusive spec. This is language that is
meant to be copied and pasted into an existing spec.
PART 1 - GENERAL
PART 2 - PRODUCTS
2.1 AUTOMATIC CONTROL VALVES
A. General:
1. All control valves shall be sized by the control vendor. All control valve bodies shall be
suitable for the static and dynamic pressures of the system. Control valve operators shall
be sized to close against a differential pressure equal to the design pump head plus 10
percent.
2. Body pressure rating and connection type construction shall conform to fitting and valve
schedules. The valve seat differential pressure rating shall exceed the design pump head
pressure.
3. Valves serving heat exchange coils and heat exchangers shall have equal percentage flow
characteristics.
4. Closed system temperature or pressure bypass valves shall have equal percentage or
linear control characteristics.
5. Open system temperature bypass valves (cooling towers) shall have linear control
characteristics.
6. Steam valves shall have linear flow control characteristics.
7. Unless otherwise specified, control valves 2 inches and smaller shall have cast iron or
bronze bodies with screwed NPT connections.
8. Valves between 2-1/2 inch and 6 inch shall have cast iron or bronze bodies with flanged
connections.
9. Do not use pneumatic actuation where valves are exposed to outdoor elements or
condensing atmospheres. All automatic control valves exposed to below freezing or
condensing ambient shall be provided with electric actuators.
10. All automatic control valves controlled by the BAS shall be furnished by the controls
contractor unless otherwise noted in these documents.
11. All automatic control valves shall be installed by the mechanical trade.
12. The controls contractor shall provide wiring as follows:
a. All line voltage power for electric valve actuators shall be wired by the controls
contractor from the nearest available power panel. Coordinate with electrical
trade.
b. All low voltage wiring between the controller and the valve actuator shall be wired
by the controls contractor.
c. All wiring between safeties and the valve actuator shall be wired by the controls
contractor.