Basic Documentation

www.usa.siemens.com/hvac 131
Magnetic Valves
MVF461HSeriesMagnetic
ControlValve.
Specications
Electrical
Low-voltageUseOnly ................................................ Class2(SELV,PELV)
24 Vac
OperatingVoltage ......................................................... 24Vac+20/-15%
Frequency ............................................................................. 45to65Hz
TypicalPowerConsumption ............................................. SeeSizingTable
Standby .........................................................<1W(ValveFullyClosed)
NominalApparentPower .................................................SeeSizingTable
SuitableFuse................................................................................... Slow
24 Vdc
OperatingVoltage ................................................................20to30Vdc
Functional Data of Actuator
Input
PositioningSignalY ........................................ 0/2to10Vdc,0/4to20mA
Impedance
0/2to10Vdc ................................................................ 100kΩ//5nF
0/4to20mA .................................................................240Ω//5nF
Forced Control
Impedance .................................................................................22kΩ
ClosingtheValve(ZconnectedtoG0) ........................ <1Vac;<0.8Vdc
Openingthevalve(ZconnectedtoG0) ........................ >6Vac;>5Vdc
NoFunction(Znotwired) ............................PositioningSignalYActive
Output
PositionFeedbackSignalVoltage ........................................0/2to10Vdc;
LoadResistance>500Ω
Current .......................................................................... 0/4to20mA;
LoadResistance<500Ω
StrokeMeasurement .................................................................Inductive
Nonlinearity ................................................................. ±3%ofEndValue
Functional Data of Valve
NominalPressure ......................................................... ANSI125(PN16)
Perm.OperatingPressure
1
.............................Waterupto248°F(120°C)
232psig(16bar)
WaterAbove248°F(120°C):188psig(13bar)
SaturatedSteam:130psig(9bar)
Pressure Differential pmax/ ps ................................... 145psi(10bar)
Materials
Body ............................................................................ NodularCastIron
CoverFlange ................................................................ NodularCastIron
Seat/InnerValve ................................................................ StainlessSteel
Packing
NormalDuty ..................................................................... EDPM(O-ring)
Electrical Connections
CableEntries ..............................................3xM20x1.5orPG13.5/G1/2
ConnectionTerminals ................. ScrewTerminalsforupto12AWGWires
Min.Cross-sectionalArea4)0.75mm
2
Max. Pressure
Max.DifferentialPressure ............................................................145psi
Media Temperature ......................................... 34°to356°F(1°to180°C)
Ambient Conditions
Temperature
Operationandstorage ................................. 23°to113°F(-5°to45°C)
Transport ................................................. -13°to158°F(-25°to70°C)
Humidity ..................................................5to95%rh(Non-condensing)
Resolution ..................................................................................... 1000:1
Position with Actuator De-energized ................................ A ABClosed
Positioning Time ...................................................................... <2seconds
Approvals ...........................................................................IP31toIEC529
ConformstoCERequirements,UL873,
CertiedtoCanadianStandardC22.2,No.24,C-TickN-474,
PED97/23/EC:Pressure-carryingParts
Par.1,Section.2.1.4/Par.3,Section3Fluidgroup2
Flow Characteristic ......................................... EqualPercentageorLinear
Environmental Protection .....................................................NEMAType1
Notes:
1
Testedat1.5xPN(24bar),similartoDIN3230-3
2
CanbeselectedviaDIPswitch.
4
Incaseofstrongvibrations,usehigh-exstrandedwires.