Basic Documentation
www.usa.siemens.com/hvac 125
MXG461...U
MagneticControlValve.
Sizing
Part No.
Line Size
(in.)
Cv
Max. Close-off
Pressure
(psi)
Power for
Transformer
Sizing (VA)
Power
Consumption
(W)
Fuse
Required
(A)
Wire Gauge
18 16 14 12
Max. Cable Length (ft.)
MXG461.15-0.6U 1/2 0.7 44 29 5 3.15 108 213 361 525
MXG461.15-1.5U 1/2 1.7 44 29 5 3.15 108 213 361 525
MXG461.15-3.0U 1/2 3.5 44 29 5 3.15 108 213 361 525
MXG461.20-5.0U 3/4 5.8 44 29 5 3.15 108 213 361 525
MXG461.25-8.0U 1 9.3 44 29 5 3.15 108 213 361 525
MXG461.32-12U 1-1/4 14 44 29 5 3.15 108 213 361 525
MXG461.40-20U 1-1/2 23 44 44 6 4.00 66 118 197 328
MXG461.50-30U 2 35 44 44 6 4.00 66 118 197 328
MXF461.65-50U 2-1/2 58 44 46 6 5.00 49 98 164 262
*
All data relates to a supply of 24 Vac.
MX..Valves with Electronic Module Product Ordering
Valve Size Cv Part No.
NPT Union
1/2" 0.7 MXG461.15-0.6U
1/2" 1.7 MXG461.15-1.5U
1/2" 3.5 MXG461.15-3.0U
3/4" 5.8 MXG461.20-5.0U
1" 9.3 MXG461.25-8.0U
1-1/4" 14 MXG461.32-12U
1-1/2" 23 MXG461.40-20U
2" 35 MXG461.50-30U
Flanged
2-1/2" 58 MXF461.65-50U*
Table Note:
*No blanking ange
Magnetic Valves