Siemens Duct temperature sensor FK-TP/200 CA1N1778E
Smart Infrastructure 2019-09-05
Equipment combinations
The FK-TP/200 duct temperature sensor can be used with all controllers which can
process the measured value from a Pt100 sensor, especially controllers from the
MULTIREG and INTEGRAL RS ranges.
Technical design
The Pt100 temperature sensor is fitted with a platinum measuring element with a
positive temperature coefficient (PTC). The measured-signal /temperature relation-
ship is linear. See data sheet 1714*) for technical information on the Pt100 sensor
element.
*) The documents can be downloaded from http://siemens.com/bt/download.
Mechanical design
The duct temperature sensor FK-TP/200 consists of a sensor probe with a con-
necting head and the inserted PT100 measuring element. The cable is connected
via a PG16 cable gland.
Mounting notes
The duct sensor FK-TP/200 should be mounted
in the middle of the air duct.
A mounting flange is supplied.
The PG16 screwed cable fitting should point
downwards. (The cable must be connected
downwards so that it leads away from the bot-
tom.) The connecting cable must be long
enough to allow mounting and dismounting of
the connected sensor without loosening the
cable connections.
9N403
Disposal
The device is considered electrical and electronic equipment for disposal in terms
of the applicable European Directive and may not be disposed of as domestic
garbage.
• Dispose of the device via the channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.