Fire Detection System Planning Guide

Emergency power supply
55
Siemens Building Technologies 007836_a_en_--.doc
Fire & Security Products 03.2004
23.3 Quiescent current table
Quiescent current when on battery operation (24V)
As basis for individual calculation of emergency power supply
The current for the 5V supply is included in these values
Module Quiescent current at 24VDC (typical) Additional current with alarm condition
B2F020 0 0
B3Q700 100mA LCD backlight ’inactive’ (active = + 200mA) + 230mA
B3Q580 20mA + 160mA
B3Q590/595 18mA + 167mA
B3R051 40mA all LEDs inactive + 2mA per activated LED
E3C011 20mA 0
E3G050 10mA all relays inactive + 11mA per activated relay
E3G060 25mA all control lines terminated + 23mA per activated control line, without external load
E3G070 25mA control line ’Horn’ terminated + 34mA without external load (horns etc.)
E3H020 100mA 0
E3I020 25mA 0
E3L020 22mA + ..mA depends from the activated device
E3L030 18mA + 40mA without external load (FBF, HM, FSK)
E3M080 85mA 37mA + 6mA per terminated line + 10mA per line in alarm
E3M111 210mA (=50mA + 0,31mA per D–Bus device) 1)
(without external 24V load)
0
K3G060 6mA + 3mA per relay
K3R072 40mA + 2mA per activated LED
0 per activated relay
Z3B171 0 + 27mA per activated relay
E3I040 15mA without external 24V load 0
K3I050 15mA + 0mA or 4mA per activated LED
K3I110 24mA max. 184mA all relay activated incl. service LED + 10mA per activated relay
+ 0,5mA per input with closed contact
1 Only valid for device with APMK = 1 (multiply value for devices > 1)