22 Power supply
22.1 Concept
The power supply for the FC700A fire detection system consists of:
Converter (mains voltage -> system voltage 29,6V)
Battery charging unit (by means of E3C011)
Batteries (lead) (capacity as required)
22.2 Special functions
Automatic battery load test
Battery charging characteristic can be programmed according to make
22.3 Application
Determine required battery capacity individually -> see chapter 23
Max. 27Ah per battery charging unit (> 27Ah = auxiliary power supply)
Parallel operation of several battery charging units possible
Battery lead without EMI-protection (battery cannot be mounted separately)
22.4 Power supply for the control unit
Battery charging module E3C011 required
I-Bus
Mains
E3C011
Batteries
AX12..
B3Q700
29,6V
FC
TF*
B2F020
40...220VA
22.5 Auxiliary power supply
* TF = Temperature sensor for battery temperature monitoring
Mains
Basic emergency
power supply
Extension
FT
B2F020
TF*
TF*
C-Bus
Batteries
AX12..
Batteries
AX12..
Monitoring via HW monitoring path
FC
Mains
B2F020
E3C011
E3C011
24V
Battery charging
unit