Fire Detection System Planning Guide

Remote transmission
50
Siemens Building Technologies 007836_a_en_--.doc
Fire & Security Products 03.2004
20 Remote transmission
Most fire detection systems are linked to a remote transmission system. Therefore
in case of alarm (alarm stage 2) the fire detection system must initiate the remote
transmission device (RT-device).
Remote transmission device
Located in cabinet of control unit
Required space depends on the type of remote transmission device
Powered by 24VDC of the fire control unit
Single channel (alarm + fault) or multi channel (several alarm channels)
Disabling/enabling via B3Q700 (FC/FT)
Interfacing
Via output contacts and special control in-/outputs of the E3G070
E3G070
B3Q700 (CPU)
I-Bus
Interfacing via E3G070
K2
24V
RT-device
FC700A
alarm fault