Fire Detection System Planning Guide

Control modules
44
Siemens Building Technologies 007836_a_en_--.doc
Fire & Security Products 03.2004
17.9 Relay outputs
B3Q700 (FT)
Z3I530
24V
Data bus
max.1000m
(Adapter)
24V
F12A100
or
F12A470
Parallel branching permissible
(not monitored)
K3R072
1
48
1
24
24 outputs
max. 30V/1A
1
24
24 outputs
max. 30V/1A
K3R072
max. 24 units,
however max.
8 addresses
1
48
1
24
24 outputs
max. 30V/1A
1
24
24 outputs
max. 30V/1A
External potential
(switchable via jumper X1......X24)
+/-
1)
1)
1)
max. 24 units,
however max.
8 addresses
Flat cable supplied with K3G060
Flat cable supplied with K3G060
+/-
B3Q700 (FC/FT)
K3G060 K3G060
K3G060K3G060
K3G060:
2 K3G060 can be connected to each K3R072
24 volt-free relay-make contact
Contacts not monitored
Contacts can be individually connected via jumper to externally supplied V+ or
V- potential
24 Relay outputs
Housing supplied by customer
K3G060
K3G060
K3R072
24 Relay outputs
17.10 Modules
Component Order-No. Description Notes
K3G060 528786 Relay card incl. flat cable Option to K3R072
Z3I530 484972 Adapter To adapt flat cable to terminals