Fire Detection System Planning Guide

Control modules
43
Siemens Building Technologies 007836_a_en_--.doc
Fire & Security Products 03.2004
17.7 Mimic Display panel outputs
B3Q700 (FT)
Z3I530
24V
Data bus
max.1000m
(Adapter)
24V
F12A100
or
F12A470
Parallel branching permissible
(not monitored)
Mimic Display panel
1
48
cable length 1m, 24 red LEDs
LED flat cable
F50F410
1
48
Mimic Display panel
cable length 1m, 24 red LEDs
B3Q700 (FC/FT)
LED flat cable
F50F410
LED flat cable
F50F410
LED flat cable
F50F410
K3R072
K3R072
Details see document 007831
K3R072:
Short circuit-protected outputs
Output for local buzzer and LED operation
Inputs for button 'buzzer switch-off' und 'lamp test'
Only suitable for the activation of LEDs
Outputs can only be allocated the statuses from one logical node
Max. 24 devices however max. 8 addresses
max. permissible length
of the data bus 1000m
Key 'Lamp test'
Key 'Switch-off buzzer'
Buzzer
LED 1....24
Short-circuit proof in-/outputs
only for housing application
inside
These in-/outputs can be in
parallel with other K3R072
if located in same cabinet
wires 49+50 for 'LED operation'
LED 25....48
wires 49+50 unused
Z3I520
Synoptic display
panel housing
B3Q700
K3R072
K3R072
17.8 Modules
Component Order-No. Description Notes
K3R072 528605 Mimic Display activation
Z3I520 484969 Cable set for K3R072 Comprises 12 cables (2-wire with connector, length=0.5m)
F50F410 529141 LED flat cable for K3R072 50-wire, 24 red LEDs, cable length 1m
Z3I530 484972 Adapter To adapt flat cable to terminals
F12A100 495275 Flat cable Micro 12-pin, 0.4m From B3Q700 (FT) to K3R072/B3R051
F12A470 495288 Flat cable Micro 12-pin, 1.5m From B3Q700 (FT) to K3R072/B3R051