Fire Detection System Planning Guide

Connection factors, line resistances and capacitances
38
Siemens Building Technologies 007836_a_en_--.doc
Fire & Security Products 03.2004
16 Connection factors, line resistances and capacitan-
ces
16.1 Terminology and abbreviations
KLK Collective line factor (SynoLINE600)
KMK Load factor for collective / conventional elements (SynoLINE600/300)
APLK addressable line factor (SynoLOOP)
APMK Load factor for addressable elements (SynoLOOP)
16.2 Collective detection line
The modules E3M080 / DC1192 have the collective line factor KLK 25
Line resistance max. 250Ω, 150 depending on evaluation required (line type 1,
11)
Line capacitance max. 4µF
The entire line from the control unit to the last detector as well as all response
indicator lines must be included when working out capacitance.
Details see document 007831
The total amount of detectors connected to one collective line should not ex-
ceed a loading factor of 25
Element Short designation Load factor KMK
Smoke detector OP620C/OP320C 1
Heat detector HI620C/622C/HI320C/322C 1
Multisensor smoke detector OH320C 1
Smoke detector DO1101-Ex 1,6
Heat detector DT1101-Ex 1
Infrared flame detector DF1101-Ex 6
Infrared flame detector DF1191/92 6
Linear smoke detector DLO1191 25
Manual call point DM1101, DM1103 1
In-/output module DC1192 1
16.3 Addressable detection line
The line module E3M111 has the addressable line factor APLK 128
Line resistance see chapter 16.4
Line capacitance see chapter 16.4
For a description of the E3M111 line module, see document 007831 'Hardware de-
scription'.
The total amount of detectors connected to one addressable line should not
exceed a loading factor of 128
Element Short designation Load factor APMK
Smoke detector OP620A, OP320A 1
Heat detector HI620A/622A, HI320A/322A 1
Multisensor smoke detector OH620A, OH320A 1
Infrared flame detector DF1191/92 5
Manual call point MT320A, DM1133 1
Input module EB322A 1
Output module AB322A 2
In-/output module ABI322A 2
In-/output module DC1192, CB320A 3
Do not install lines longer than 2000m