Fire Detection System Planning Guide

Specify hardware required
23
Siemens Building Technologies 007836_a_en_--.doc
Fire & Security Products 03.2004
9 Specify hardware required
In order to be able to specify the hardware required, system key data must be
specified according the following procedure:
1. Specify number and type of detection lines
Dependent on:
Detector series
Number of detectors, input and output modules
Building structure
2. Specify number and type of fire control installations
Dependent on:
The fire protection installations to be activated
Location of the contacts (centralized or decentralized)
Individual types of contact (250VAC/10A or 30VDC/1A)
3. Specify number of operating units
Dependent on:
Operating concept
Parallel indicator panels, fire department control panels
4. Specify Accessories required
Dependent on:
Printer interface and printer
Remote transmission equipment
Gateway, etc.
5. Specify emergency power supply battery capacity
Dependent on:
Total quiescent current
Required emergency current operating period (according to country)
Type of remote transmission
6. Provide configuration sheet/sheets (see chapter 29)
Dependent on:
Select sheets corresponding to the configuration
Complete everything