FC360 Panel Configurator FC360 Desktop Editor Operation Manual A6V10450595_en--_b 2016-11-08 Building Technologies Control Products and Systems
Legal notice Legal notice Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd.
Table of Contents 1 About this document ................................................................................... 5 1.1 Applicable documents ..................................................................................... 6 1.2 Abbreviations ................................................................................................... 7 1.3 Download center ............................................................................................. 7 1.4 History of changes......
| 36 Building Technologies Fire Safety A6V10450595_en--_b 2016-11-08
About this document Applicable documents 1 1 About this document Goal and purpose This document describes the configuration of FC360 fire detection system by using ‘FC360 Panel Configurator’ and 'FC360 Desktop Editor'. Scope The information in documents A6V10421795 is prerequisite for configuration of the fire detection system with ‘FC360 Panel Configurator’ and 'FC360 Desktop Editor'.
1 About this document Applicable documents ID code Examples ID_languageCOUNTRY_version -- = multilingual or international A6V10215123_deDE_a A6V10215123_en--_a A6V10315123_----_a Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD). Reference document and source language ● ● The source language of this document is English (en). The reference version of this document is the international version in English.
About this document Abbreviations 1 1.2 Abbreviations Abbreviations Explication AVC Alarm Verification Concept EOL End of Line MCP Manual Call Point PSU Power Supply Unit PMI Person Machine Interface EVAC Evacuation GUI Graphical User Interface EMC Electro Magnetic Compatibility 1.3 Download center You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address: http://siemens.
1 About this document History of changes 1.4 History of changes The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version. The table below shows this document’s history of changes: Version Edition date Brief description b 2016-11-08 Delete user manuals and Eng. Manuals information in chapter 5.
Introduction 2 2 Introduction Two tools are used to configure FC360 system easily and conveniently: ● FC360 Panel Configurator ● FC360 Desktop Editor The below table describes the functions of the tools: Tools Functions FC360 Panel Configurator ● ● ● ● ● ● Online configuration Apply configuration Backup configuration Restore configuration Reset alarm counter Synchronize system time FC360 Desktop Editor ● ● Update firmware Modify configuration file ‘FC360 Desktop Editor' is available at www.
3 Installation Connect PC to panel 3 Installation 3.1 Connect PC to panel A PC is required for most commissioning, maintenance and repair work. The figure below shows the connection between PC and panel. 11 X26 X26 Terminal of PC connection 1 Cable, type CAT 5 or CAT 7, crossover, max.
Installation Exit software 3 3.2.2 'FC360 Desktop Editor' 'FC360 Desktop Editor' can be started as follows: 1. Double click the software shortcut icon on the desktop or – In the taskbar, click 'Start' > 'Programs' > 'Siemens' > 'FC360' > 'FC360 Desktop Editor'. 2. Select 'Language:'. 3. Click 'Enter'. 4.
4 GUI Overview of program window 4 GUI 4.1 Overview of program window 1 Title 2 Task cards 3 Information on the selected task card 4 Toolbar 5 Quick guide 6 Information on country and access level 1 1 12 | 36 Building Technologies Fire Safety Applies to 'FC360 Panel Configurator' only.
GUI Task card 4 4.2 Task card Task Function Site Configures site information. Detection & Control Modifies device property and configures site specific setup (i.e. zone and section assignment). Cause & Effect Configures logic controls. Administration 1 ● ● ● ● Other settings Configures special settings. 1 Building Technologies Fire Safety Changes password of access levels 2 / 3 / 3.1. Uploads event memory from panel to PC. Uploads test report from panel to PC.
4 GUI Toolbar 4.3 Toolbar 4.3.1 'FC360 Panel Configurator' Tool Function Apply Downloads the current configuration to the panel (takes effect immediately). Backup There are two options: ● Backup current panel’s configuration to PC ● Backup all changes in current browser to PC Restore Restores / downloads an existing configuration from PC to panel. About Shows 'FC360 Panel Configurator'' version, Panel software version, Output card (4M) version and P2 UART version.
Program operation 'Site' task card 5 5 Program operation This chapter describes how to configure the FC360 fire alarm system. 5.1 'Site' task card Command Functionality Reset alarm counter 1 1 Sets alarm count to 0. Applies to ''FC360 Panel Configurator' only. Field Functionality Name Inputs site name. Installer name Contact 1 tel. 1 Service reminder enable Inputs installer name. Inputs contact telephone (only number 0…9 possible).
5 Program operation 'Site' task card 16 | 36 Building Technologies Fire Safety Field Functionality Timed channel active The output is activated at the set time if the logic control between 'Timed Channel' (Cause) and outputs (Effect) in the 'Cause & Effect' task card is configured. Timed channel inactive The output is deactivated at the set time if the logic control between 'Timed Channel' (Cause) and outputs (Effect) in the 'Cause & Effect' task card is configured.
Program operation 'Site' task card Field Functionality AVC T2 time Selects investigation time T2 from the following: ● 2mins ● 2.5mins ● 3mins ● 3.5mins ● 4mins ● 4.5mins ● 5mins (default) ● 5.5mins ● 6mins ● 6.5mins ● 7mins ● 7.5mins ● 8mins ● 8.5mins ● 9mins ● 9.5mins ● 10mins Allowed time under EN 54-2 is T1+T2 ≤10 min. Timed switching to unmanned ● ● 1 Building Technologies Fire Safety 5 Checkbox activated: Automatically switches from 'Manned' to 'Unmanned'.
5 Program operation 'Detection & Control' task card 5.2 'Detection & Control' task card 1 Toolbar 2 Information view on the selected task card 3 Devices icons 1 4 'Device Properties' view 5 Task cards Command Functionality Edit device 1 Checked: devices icons and 'Add sounder base' & 'Delete device' commands are displayed. You can drag the icons to the information view if you want to add a new device.
Program operation 'Detection & Control' task card Task Functionality Loop Configures devices on the loop. Stub 1 Configures devices on the stub1. Stub 2 Configures devices on the stub2. Onboard IO Configures sounder lines, programmable IO, relays on mainboard. Output card 4M Configures outputs on output card (4M). Com. interface Configures RS232 module. 5 The loop view and stub1 / stub2 view cannot be configured simultaneously. It depends on the C-NET topology. 5.2.
5 Program operation 'Detection & Control' task card Detector parameter set Devices Parameters Functionality OP720 Sensitivity Selects sensitivity from the following: ● 01: Standard (Default) ● Sensitive HI720 Detection method Selects detection method from the following: ● A2S ● A2R (Default) HI722 Detection method Selects detection method from the following: ● A2S (Default) ● A2R OH720 Sensitivity Selects sensitivity from the following: ● Robust (Default) ● Sensitive OOH740 Parameter set
Program operation 'Detection & Control' task card 5 Sounder base Device Parameter Functionality DBS720 Volume Specifies sound level in the activated status. Selects volume from the following: ● High ● Medium Alarm sounder and interbase Device Parameter Functionality FDS221 FDS229 DBS721 DBS728 DBS729 Location Inputs location text. Volume Specifies sound level in the activated status.
5 Program operation 'Detection & Control' task card Input/output module Device Parameter Functionality FDCIO221 FDCIO222 FDCIO224 Location Inputs location text. Short circuit monitoring enabled ● ● 22 | 36 Building Technologies Fire Safety Checkbox activated (Default): monitors the input line for short circuits. Checkbox deactivated: input is not monitored for short circuits.
Program operation 'Detection & Control' task card 5 Zone Module Device Parameter Functionality FDCI723 Location Inputs location text. Response time setting Selects response time from the following: ● Alarm:0s/Malfunction:10s (Default) ● Alarm:15.5s/Malfunction:10.5s ● Alarm:16s/Malfunction:11s ● Alarm:17.5s/Malfunction:12.
5 Program operation 'Detection & Control' task card Floor repeater Display / Floor repeater terminal Device Parameter Functionality FT2010 FT2011 Location Inputs location text. User PIN ● Inputs device configuration PIN. ● ● Checkbox activated: faults can be displayed. Checkbox deactivated (Default): faults are not displayed. 1. List faults 2. Not used 1 Not used. 1 3. List isolations 1 4. List technical messages 1 ● ● Checkbox activated: isolations can be displayed.
Program operation 'Detection & Control' task card 5 5.2.2 Configure onboard IO The panel mainboard has two sounder lines, four configurable IOs and three relays. The customer specified text can be modified in the information view. Some specified properties can be modified in ‘Device Property’ view. Sounder line Customer text can be modified and no other properties are available.
5 Program operation 'Detection & Control' task card Relays Field Functionality contact usage Selects 'contact usage'' from the following: ● RT fire (Default for Relay 1) ● RT fault (Default for Relay 2) ● Fire alarm (Default for Relay 3) 5.2.3 Configure output card (4M) The output card (4M) has four configurable outputs. The default setting for the outputs are: ● OUT1: RT fire ● OUT2: RT fault ● OUT3 / OUT4 : Sounder line The customer specified text can be modified in the information view.
Program operation 'Detection & Control' task card 5 5.2.4 Configure communication interface Communication mmunication interface configures the RS232 module connected to the event printer. RS232 module Text column is editable. None of these parameters can be changed. Refer to these parameters to configure the external printer.
5 Program operation 'Cause & Effect' task card 5.3 'Cause & Effect' task card Logic controls are configured in the ''Cause & Effect'' task card. After the panel executes 'Auto 'Auto-configure' configure' or you manually assign devices to corresponding zones, all possible causes are listed in the left column and all possible control outputs are list listed ed on the top row. All possible controls between cause and effect are marked with circles or dropdown lists where the column and line intersect.
Program operation 'Administration' task card 5 5.4 'Administration' task card This chapter is only available for 'FC360 Panel Configurator'. Command Functionality Synchronize system time Synchronizes panel time with PC time. with PC Restore factory setting Restores panel configuration to factory setting. Save configuration summary Exports the current configuration to a readable CSV file. Change password of access level 2 / 3 / 3.
5 Program operation 'Administration' task card System Info Field Button Functionality Event memory Upload to PC Uploads event memory to PC. The data is saved as a CSV file. Test report Upload to PC Uploads test report to PC. The data is saved as a CSV file. Quick guide Field Button Functionality Site documents Upload to PC Uploads site documents to PC with ZIP file. Download to panel (AL3) Downloads site documents to panel with ZIP file.
Program operation 'Other settings' task card 5 5.5 'Other settings' task card Field MCP broken glass message Functionality 1 ● ● Checkbox activated: 'Glass Broken Device’ message will be displayed after detector line reset (ACK + Reset) when an MCP remains activated (i.e. glass not replaced). Checkbox deactivated: a new alarm will be reported when the panel restarts the detector line e and the MCP is still activated.
5 Program operation 'Other settings' task card Field Functionality Acknowledge availability at access level I ● ● Checkbox activated: The button is available at access levels 1, 2 and 3. Checkbox deactivated: The button is available at access levels 2 and 3. Block ackn./reset if RT is active ● Checkbox activated: and button on FT2010 and configured input used as ‘Acknowledge’ and ‘Reset’ are blocked if ‘Fire brigade is called’ is activated.
Program operation 'Other settings' task card Field Functionality Enable DHCP server ● 5 Checkbox activated: tivated: Panel distributes an IP address to PC. On PC side you can configure the network connection between PC and panel at the below window: 1. Obtain an IP address automatically (We recommend using the Windows default setting) 2. Use the following IP address (not recommended) – IP address: 192.168.251.xxx (xxx can be 1-254, 254, 100 cannot be used) – Subnet mask: 255.255.255.
6 Troubleshooting PC disconnect from panel 6 Troubleshooting 6.1 PC disconnect from panel The following information dialog is displayed if you are using ''FC360 Panel Configurator Configurator' and PC disconnects from the panel: Action: 1. Check cable connection. 2. Click . a 'FC360 FC360 Panel Configurator Configurator' restarts.
Troubleshooting PC disconnect from panel Building Technologies Fire Safety 6 35 | 36 A6V10450595_en--_b 2016-11-08
Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID: A6V10450595_en--_b Edition: 2016-11-08 © Siemens Switzerland Ltd, 2016 Technical specifications and availability subject to change without notice.