9 Maintenance
9.1 General
The fire detection installation requires only little maintenance work. It has a high
degree of self monitoring, such as
detectors monitored on presence, lines on wire break and short circuit
call points monitored on broken glass, lines on wire break and short circuit
control lines monitored on wire break and short circuit
battery monitored on presence and capacity
permanent system checking by watchdog function
programmed user functions are stored in FLASH-memory
9.2 Recommended system performance checks
We recommend the following schedule for the system performance checks. How-
ever, possible local national regulations have priority.
Alarm organization
Interval in years Performance checks
1 2 5
Check the functioning of delay times V1 and V2 X
Verify switchover mode manned to unmanned and vice versa manually X
Activate automatic detectors while system is set to mode unmanned X
Activate automatic detectors while system is set to mode manned X
Activate manual call points X
Check activation of remote transmission equipment X
Alarm horn
Interval in years Performance checks
1 2 5
Activate alarm horn test and check all acoustic alarm devices X
Detector network
Interval in years Performance checks
1 2 5
Activate one detector within each line and verify zone assignment and
parameters
X
Check all detectors and call points visually X
Activate all detectors and manual call points X
Check each detection line whether a short circuit or open line activates a
fault
X
Overhaul all automatic detectors at the factory
– at latest after 5 years in clean environment, otherwise earlier
X
Refer also to the corresponding detector manuals
Fire control installations
Interval in years Performance checks
1 2 5
Check activation of each fire control relay X
Check correctness of each shutdown operation X