8.3.6 Step 6, measures against false alarms
LED zone 1 - x Option Setting Key
Red yellow
Function: Zone with alarm verification
1 no alarm verification Default off
2 Alarm only if second Alarm within 60 sec.
1st alarm = automatic Reset with short flash up of zone
LED
zone 1 – x
on
Function: Zone disabled in mode manned
3 not disabled Default off
4 disabled as long as mode manned is active
zone 1 – x
on
Note: These measures are only justified on severe environmental conditions.
8.3.7 Step 7, control lines on alarm
LED zone 1 - x Option Setting Key
Red yellow
Function: Zone with not activated control lines on Alarm
1 both control lines activated Default off
2 both control lines not activated on on
3 control line 1 not activated on
4 control line 2 not activated
zone 1 - x
on
8.3.8 Step 8, special zone parameters
LED zone 1 - x Option Setting Key
Red yellow
Function: Behavior on Alarm immediately after Reset
1 renewed Alarm Default off
2 alarm < 15 sec. after Reset initiates line Fault
zone 1 - x
on
Function: Driver output per zone
3 active if zone is on Alarm
remains until Reset
Default off
4 active if zone is on Alarm, Fault, Disabled or Test
remains until Reset or state inactive
zone 1 - x
on
8.3.9 Step 9 not used
8.3.10 Step 10, detector line short or break
LED zone 1 - x Option Setting Key
Red yellow
Function: Zone state self-hold on Alarm
1 state line short / break = Fault Default off
2 state line short = Alarm 2
state line break = Fault
on
3 state line break = Alarm 2
state line short = Fault
on
4 state line short = Alarm 1
state line break = Fault
zone 1 - x
on on