User Manual
Configuration 
35 
Building Technologies   A6V10265083_a_en_--
Fire Safety & Security Products    03.2010
8.3.3  Step 3, zone processing on alarm 
LED zone 1 - x Option Setting  Key 
Red yellow 
Function: Zone alarm processing (zone type) 
1 via timer V1/V2 Default off 
2  direct (timer bypassed) 1) on  
3  Alarm 0 (internal) 1) 
- RT and timer V1/V2 not initiated 
- Horn activated (unless disengaged in step 7) 
 on 
4 via timer V1/V2, but call points always initiate 
Alarm 2 (direct) 
 see also chapter 5.1.4 manual, manual call 
point detection 
Zone 1 - x 
on on 
1) 
If all zones are set to direct or internal, the function manned/unmanned is disabled. 
8.3.4  Step 4, LED activation mode 
LED zone 1  LED zone 2 Option Setting  Key 
Red yellow Red yellow 
Function: Activation of LED remote transmission 
1 on RT-Alarm only  Default 
off 
2 on RT-Alarm and RT-Fault 
zone 1 
on 
Function: Flashing mode of the two LED Alarm 
3 alternating while V1/V2 run  Default 
off 
4 simultaneously on unacknowledged alarms
zone 1   
on 
Function: LED system part disabled on mode manned 
5  off in mode manned off 
6  on in mode manned  
zone 2   
Default 
on 
Function: Resound or not on new alarm 
7  Resound sounders on new alarm  Default 
off 
8  No resound on new alarm 
Zone 2 
+ key 2 
on 
8.3.5  Step 5, activation mode of control lines 
LED zone 1 – 6 Option Setting  Key 
Red yellow 
Function: Activation mode of control lines 1-6 
1 continuous on Alarm 1 and 2 Default off 
2 continuous on Alarm 1 
pulsating on Alarm 2 
on 
3 pulsating on Alarm 1 
continuous on Alarm 2 
slow 
4 pulsating on Alarm 1 and 2 fast 
5 continuous on Alarm 1 
not activated with Alarm 2 
on on 
6 pulsating on Alarm 1 
not activated with Alarm 2 
slow on 
7  not activated with Alarm 1 
continuous on Alarm 2 
on slow 
8  not activated with Alarm 1 
pulsating on Alarm 2 
slow slow 
9 don't use  on fast 
10 don't use  fast on 
11 continuous on RT-Alarm 
–  same facility as RT-Alarm 
 on 
12 continuous on Alarm 1 and 2 
–  same facility as driver output (fire con-
trols) 
 slow 
13 continuous on Alarm 2 
–  same facility as driver output (fire con-
trols) 
 fast 
14 continuous on RT-Fault 
–  same facility as RT-Fault (until inactive) 
–  possible with control line 6 only 
zone 1 = control line 1 
zone 2 = control line 2 
zone 3 = control line 3 
zone 4 = control line 4 
zone 5 = control line 5 
zone 6 = control line 6 
control lines 3 – 6 with 
8/12 zone panel only and 
additional control card 
fast fast 
Option 1 to 13 active until Reset 