User Manual
Operation and indicator elements, mode of operation (PMI) 
26 
Building Technologies   A6V10265083_a_en_--
Fire Safety & Security Products    03.2010
6.2.3  Set clock 
Set date and time 
1. Give operating access on level 2 
–  the system may not display any alarm or fault 
2. Hold key reset, key in 4233, release key reset and confirm by pressing key ac-
knowledge 
–  LED manned and operating access flash alternately and display shows 
"1_.XX" 
3. Set year with the numeric key 1 (>) or key 2 (>) 
–  confirm setting with zone key 1 then press key reset to proceed to next option 
(month, day, etc.) or press key acknowledge to proceed to previous option 
4. To end input sequence, press numeric key 4 
–  timeout 3min after last entry 
–  automatic stop after alarm or fault 
Display Option  Selection  Setting digit 3 and 4 
digit 1  digit 2  dot  digit 3  digit 4 
1  Year (03 to 99)  1  X  X 
2  Month (01 to 12)  2  X  X 
3  Day (01 to 31)  3  X  X 
4  Hour (00 to 23)  4  X  X 
5  Minute (00 to 59) 
  with numeric key 1 = up 
  with numeric key 2 = down 
5 
--- 
X X 
6  Adjustment +/- 20sec per day  key 1 to set clock 1-20sec faster 
key 2 to set clock 1-20sec slower 
6 - (-) 
=
 (+) 
. 
x x 
It is only possible to go to the next option if the current entry is completed and ac-
cepted; otherwise, the buzzer will sound. 