Operating instructions
Maintenance 
28 
Siemens Building Technologies   007995_a_en_--.doc
Fire & Security Products    04.2004
6.3  Check control unit 
Overview 
This test intends to check whether the optical and acoustic elements of the control 
unit function faultlessly. 
Procedure 
Check the control unit as follows: 
1. Press the key 'Lamp test/Sounder test' 
 The buzzer sounds. 
 All LEDs light up. 
2. Check whether all LEDs light up and the buzzer sounds. 
6.4 Simulate alarm 
Overview 
By simulating an alarm you can check the following functions of the fire detection 
system: 
 Remote transmission (e.g. transmission to the fire brigade) 
 Alarming devices (e.g. horns and flashlights). 
 Fire control installations 
WARNING! 
Before simulating an alarm, inform the fire brigade to avoid an unnecessary 
turning out. 
WARNING! 
Activate the fire control installations only when you are sure that no damage will 
occur. When you are not sure, switch the fire control installations off. 
Procedure 
Simulate an alarm as follows: 
1. Inform accordingly (e.g. the fire brigade) on the pending simulation. 
2. Press the numerical key '1' and keep it pressed. 
3. Press the zone key '1'. 
 Alarm is simulated. 
 The red zone LED lights up. 
 The alarm sequence has been activated. 
4. Check whether the alarm sequence is correct. Zones with manual call points will 
trigger alarm immediately. Zones with automatic detectors will trigger alarm after 
the expiry of the delay periods V1 and V2. 
5. Check whether the fire control installations have responded correctly. 
6. To finish the simulation, press the key 'Acknowledge', then the key 'Reset'. 
7. Repeat steps 2 to 5 for all zones. 