Operating instructions
Operation 
24 
Siemens Building Technologies   007995_a_en_--.doc
Fire & Security Products    04.2004
5.6.6  Temporarily blocking remote transmission of alarms 
Overview 
If in exceptional cases alarms shall not be remotely transmitted, the remote trans-
mission of alarms must be blocked. 
WARNING! 
Remote transmission functions that have been blocked are not activated in case 
of an alarm! For this reason, always enable blocked remote transmission func-
tions again as soon as normal operating conditions are prevailing again! 
Procedure 
To block the remote transmission of alarms, please proceed as follows: 
1. Enable the operating level 2 (password or key). 
2. Press the key 'RT-ALARM Disable/Enable' twice. 
 The yellow LED 'RT-ALARM' lights up. 
 The remote transmission of alarms is now blocked and you can carry out the 
intended work. 
3. To switch the remote transmission of alarms on again, press the key 'RT-Alarm 
Disable/Enable' twice. 
 The yellow LED 'RT-ALARM' no longer lights up. 
 The remote transmission of alarms is enabled again. 
5.6.7  Temporarily blocking remote transmission of alarms & faults 
Overview 
If in exceptional cases alarms or faults shall not be remotely transmitted, the re-
mote transmission of alarms and faults must be blocked. 
WARNING! 
Remote transmission functions that have been blocked are not activated in case 
of an alarm or fault! For this reason, always enable blocked remote transmission 
functions again as soon as normal operating conditions are prevailing again! 
Procedure 
To block the remote transmission, please proceed as follows: 
1. Enable the operating level 2 (password or key). 
2. Press the key 'RT-ALARM Disable/Enable' three times. 
 The yellow LEDs 'RT-FAULT' and 'RT-ALARM' light up. 
 The remote transmission of alarms and faults is now blocked and you can 
carry out the intended work. 
3. To switch the remote transmission on again, press the key 'RT-ALARM Dis-
able/Enable' once. 
 The yellow LED 'RT-FAULT' and 'RT-ALARM' no longer light up. 
 The remote transmission of alarms and faults is enabled again. 