10 Trouble shooting
10.1 Interpretation of fault LED flashing
1234
1
2
3
4
5
6
7
8
LED LED LED
9
10
11
12
13
14
15
17 (23)
16
9 9 9 9
LED LED flashing Cause / Action to be taken
9 Fault There is a fault in the system
check if there is another fault LED flashing, if not
check if control input Fault is activated
10 Earth fault Any part of the system has a leakage to earth
Remove one external line (detector line etc.) after the other until the fault disappears, then repair
the defective line
if no external line has a leakage to earth replace mainboard
11 Power fault
Flashing fast
Flashing slow
Battery is disconnected or low
Replace battery
Mains supply is missing (after delay has expired)
Check internal fuse or external mains breaker
12 System fault The microcomputer has failed (system not working)
Switch power off and restart, if fault continues replace mainboard
13 Alarm horn fault There is a fault in the monitored control lines (horn)
Check line for a short circuit or break or missing/defective EOL
14 Fire controls fault There is a fault on a monitored control line (programmed in step 5 to option 12 or 13)
Check line for a short circuit or break or missing/defective EOL
15 RT-Fault Control input Fault RT is active, or if programmable control input with option 1 is active (Fault re-
mote transmission device)
Check remote transmission device
There is a fault on a monitored control line (programmed in step 5 to option 14)
Check line for a short circuit or break or missing/defective EOL
23 RT-Alarm There is a fault on a monitored control line (programmed in step 5 to option 11)
Check line for a short circuit or break or missing/defective EOL
Yellow LED
zone x
Fault zone There is a fault in zone number x
Check whether any detector head is removed
Check line for short circuit or break or missing/defective EOL
Display Indicates 88.88 Clock not set (with new system start up or after power down)
Set date and time
EVAC module
2 Fault EVAC control
line
Corresponding EVAC control line is interrupted or has a short circuit
Check line for a short circuit or break or missing/defective EOL
5 Fault EVAC control
line
One or more EVAC control lines are interrupted or have a short circuit
also LED 9 Fault in fire control unit is active.
Check line for a short circuit or break or missing/defective EOL