User Manual

Configuration
40
Building Technologies A6V10265083_b_en_NL
Fire Safety & Security Products 04.2010
8.3.22 Step 31, allocate detector zones to EVAC control lines
LED
Zones
1 – 8 1 2 3 4
Option Setting Key
red yellow yellow yellow yellow
1 No allocation Zone 1-8 Default off
2 In case of alarm 1, activate
EVAC control line 1
numeric 1
on
3 In case of alarm 1, activate
EVAC control line 2
numeric 2
on
4 In case of alarm 1, activate
EVAC control line 3
numeric 3
on
5 In case of alarm 1, activate
EVAC control line 4
numeric 4
on
on
Procedure
1. Select programming step 31
2. Select detector zone
==> red zone LED lights up
3. Press numeric key x (1 – 4)
to allocate the selected detector zone on alarm 1 to the control line x (1 – 4)
==> yellow zone LED x (1 – 4) lights up
Notes
Options 2 to 5 can be applied simultaneously. In other words, an alarm on a de-
tector zone can be allocated to several EVAC control lines.
It is possible to activate the EVAC control lines only with alarm 2 instead of
alarm 1 (refer to programming Step 32, change activation of EVAC control lines)
Exit from the programming mode on Step 31, allocate detector zones to EVAC
control lines, is not possible. It requires the selection of another programming
step to exiting from programming mode.
8.3.23 Step 32, change activation of EVAC control lines
LED zone 1 LED zone 2 Option Setting Key
red yellow red yellow
Function: change alarm stage to activate EVAC control lines
1 EVAC control lines are activated with
state alarm 1
off
2 EVAC control lines are activated with
state alarm 2
zone 1
on
Notes
Option 1 or 2 applies for all allocations from any detector zone