User Manual

Configuration
38
Building Technologies A6V10265083_b_en_NL
Fire Safety & Security Products 04.2010
8.3.14 Step 14, delay mains failure
8.3.15 Step 15, special parameters
LED zone 1 LED zone 2 Option Setting Key
red yellow red yellow
Function: Acknowledge and Reset from external blocked during RT alarm active
1 not blocked Default off
2 blocked
zone 1
on
Function: Zones set to option 2 in step 10 with special disabling procedure
3 not activated Default off
4 alarm on line short even if zone is disabled
zone 1
on
Function: RT-Fault and RT-Alarm disabled if state operating access is provided
5 not disabled Default off
6 disabled
zone 2
on
Function: All zones with option 1 in step 3 react like option 4
7 not activated Default off
8 activated
zone 2
on
8.3.16 Step 16, programmable control input
LED zone 1 LED zone 2 Option Setting Key
red yellow red yellow
Function: Programmable control input
1 initiate Fault remote transmission device Default off
2 provide operating access on
3 initiate state Evacuation 1)
zone 1
on
4 disable RT-Alarm + RT-Fault on
5 de-activate mode manned (pulse)
on
6 initiate mode manned
zone 2
on on
Options 1 to 4 and 6: active as long as positive potential is applied
1)Evacuation will be activated even if jumper evacuation is set to off