User Manual
Configuration
34
Building Technologies A6V10265083_b_en_NL
Fire Safety & Security Products 04.2010
8.3 Programmable functions
1234
4
3
2
1
7
3
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
4 5
6
9 9 9 9
4
Procedure
1. Select the desired step with key (2) or (3)
2. Press the zone keys (6) as many times until the desired option is indicated with
the corresponding zone LED (5) according to the following tables.
8.3.1 Step 1, timer V1
LED zone 1 LED zone 2 Option Setting Key
red yellow red yellow
Function: Timer V1 on alarm or fault in mode manned
1 0.5min Default off
2 1min on
3 2min
zone 1
on
4 3min on
5 4min
zone 2
on
8.3.2 Step 2, timer V2
LED zone 1 LED zone 2 Option Setting Key
red yellow red yellow
Function: Timer V2 on alarm in mode manned
1 2min Default off
2 3min on
3 4min
zone 1
on
4 5min on
5 6min
zone 2
on
LED zone 3 LED zone 4
6 7min on
7 8min
zone 3
on
8 9min on
9 10min
zone 4
on
Warning EN54-2 requires that the time V1 + V2 is no longer than 10 min.