User Manual

Configuration
32
Building Technologies A6V10265083_b_en_NL
Fire Safety & Security Products 04.2010
8.2 Programming steps
1234
4
3
2
1
7
3
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
4 5
6
9 9 9 9
4
The selected programming steps are indicated at display module (4). The setting of
an option can be selected with the zone keys (6) and is indicated with the corre-
sponding red and yellow zone LED (5).
Select a programming step
press key (3) to move upwards
press key (2) to move downwards
Basic programming steps
LED STEP Define function
1 Timer V1
2 Timer V2
3 Processing of zone Alarm (zone type)
4 LED activation mode
LED Remote transmission
LED Alarm
LED System part disabled mode manned
Resound or not on new alarm
5 Activation mode of control lines 1 - 6
6 Measures against false alarms
alarm verification
zone disabled in mode manned
7 Control lines on Alarm
on
8 Special zone parameters
behavior on immediate Alarm after Reset
function of zone control outputs
9 Not used
10 Detector line evaluation on line short or line break
11 Cross-zoning
12 Access code (password)
operating access
13 Special PMI parameters
reminder beep on fault and system part disabled
Fault messages to be Reset
Suppress battery fault
14 Not used
15 Special parameters
external Acknowledge and Reset
zones with special disabling procedure
Remote transmission on operating access
all zones with option 1 in step 3 react like option 4
flashing
16 Programmable control input
Do not assign functions cross zoning (step 11) and alarm verification (step 6) simultaneously to the
same zone!