8 Configuration
8.1 Programming user functions
In order to fulfill the local requirements, the programmable user functions may be
adjusted by the single programming steps.
1234
4
3
2
1
7
3
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
4 5
6
9 9 9 9
4
Procedure to enter programming mode
1. Set system to state non-alarm and provide operating access level 2
2. Hold key (3) and press numeric keys (7) 1, 4, 2, 4, 2, 3, 2, 1 one after the other
Continuous top-down flash up of LED block (1); indicates mode programming
Procedure to exit programming mode
1. Press numeric keys (7) 1 and 4 simultaneously
automatic timeout if no further key is pressed for more than 4min; LED block
(1) stops flashing
Poll checksum
see under Poll service informations
Set user functions to factory default settings
The user functions of all programming steps can be set to factory default values
with one operation.
1. Disconnect mains and battery
2. Press and hold numeric keys (7) 1, 2, 3, 4 simultaneously followed by reconnect-
ing mains
LED block (1) starts flashing
3. Release numeric keys (7)
4. Press numeric keys (7) 1, 2, 3, 4 simultaneously again
LED block (1) stops flashing and double beep of buzzer occurs
System is now set to default
5. Reconnect battery
Note:
For factory default settings
see Log sheet for programmed user functions