6.2 EVAC module
Operating panel
The EVAC module has a separate operating panel integrated in the unit. The panel
basically consists of LED and keys.
System ON
Stop
All call
Fault
Disabled
Start
Buzzer off
on/off
Lamp test
EVACUATION
ground floor west
1st floor west
2nd floor west
3rd floor west
LED 3
LED 4
LED 5
LED 1
LED 2
LED 6
Key 6
Key 7
Key 2
Key 1
Key 1
Key 1
Key 1
Zone 1
Zone 2
Zone 3
Zone 4
Key 3
Key 4
Key 5
LED 1
LED 2
LED 1
LED 2
LED 1
LED 2
Bedrijf
Totaal Alarm
Storing
Uitgeschakeld
Zoemer uit
In/Uit
LED Test
ONTRUIMING
1 VERD. west
2 VERD. west
3 VERD. west
4 VERD. west
Zone 1
Zone 2
Zone 3
Zone 4
Stop
Start
LED 3
LED 4
LED 5
LED 1
LED 2
LED 6
LED 1
LED 2
LED 1
LED 2
LED 1
LED 2
Function of LED
LED State Bedeutung
lighting up Corresponding EVAC control line is active LED 1
flashing (max. 5
sec)
Key 1 was pressed
lighting up Corresponding EVAC control line is switched off LED 2
flashing Corresponding EVAC control line is interrupted or has a short circuit
LED 3 lighting up EVAC module is ready
LED 4 lighting up One or more EVAC control lines are switched off; in this case, part of system OFF is displayed in the unit.
LED 5 flashing One or more EVAC control lines are interrupted or have a short circuit; in this case, also General Fault in fire
control unit is active.
lighting up All EVAC control lines are active LED 6
flashing (max.
5s)
Key 2 was pressed
Function of keys
Key Function Operating Access
1 Select one EVAC control line (1 – 4) (see following description) always
2 Select all EVAC control lines (1 – 4) (see following description) always
3 Switches off buzzer in case of a fault in the EVAC module always
4 Manual activation of the selected EVAC control line (see following description) always
5 Manual deactivation of the selected EVAC control line (see following description) always
6 Switching on/off of the selected EVAC control line via operating access level 2
7 Short-time activation (5 sec) of all LEDs and of buzzer for control purposes always
Manual activation/deactivation of EVAC control lines
1. Press corresponding EVAC control line key (1) or (2) for all EVAC control lines
2. Within 5 seconds, press key Start (4) to activate or press key Stop (5) to deacti-
vate the control line.
Switching on/off of the EVAC control lines
1. Enable operating access level 2
2. Press corresponding EVAC control line key (1) or (2) for all EVAC control lines
3. Press key on/off (6) to switch on/off EVAC control lines