5.3 Event processing
5.3.1 Alarm
The processing of alarm events is programmable mainly to prevent the unneces-
sary turnout of fire department for minor incidents. It involves personnel in the
alarming sequence and relies on the operating mode manned. The system has to
be run in operating mode manned as long as the responsible personnel is present.
Mode manned has to be de-activated if the responsible personnel leaves the build-
ing.
Programmable parameters
Zone type
via timer V1/V2 in mode manned ; for detectors
direct ; for manual call point, sprinkler alarms, etc.
internal ; for non-fire-events, e.g. technical alarm
Timer for detector zones in mode manned
range of V1 0.5 ... 4min; time to acknowledge the system before RT-Alarm is ini-
tiated
range of V2 2 ... 10min; time to investigate the fire incident before RT-Alarm is
initiated
5.3.2 Processing diagram
‘V1’
state ‘ALARM 1’
zone output activated
start timer ‘V1’
Decision
ALARM
mode ‘manned
ALARM
manual call point zone
mode ‘manned’
no influence
state ‘ALARM 2’
Buzzer & sounders (re-) activated
control lines(re-) activated
contact RT-Alarm activated
Reset
V1 expired ?
acknowledged ?
V2 expired ?
minor incident ?
Start timer ‘V2’
Zone type ‘via timer V1/V2’ Zone type ‘direct
ALARM
mode ‘unmanned
state ‘ALARM 0’
buzzer activated
sounders activated
zone output activated
ALARM
mode ‘manned’
no influence
Zone type ‘intern’
fire ?
activate next call point
or
press key
‘cancel alarm delay’
none fire zone
fire detector zone
fire detector zone
buzzer activated (continuous)
sounders activated
activate next call point
or
press key
‘cancel alarm delay’
If all zones are set to zone type direct or internal then mode manned cannot be ac-
tivated.
Alarm 0: The activated mode for the monitored control lines are programmed in to step 5.
Only the monitored control lines will be aktivated, which are programmed to "Alarm 1" in step 5.