User Manual

Function and design
18
Building Technologies A6V10265083_b_en_NL
Fire Safety & Security Products 04.2010
5.2.4 Evacuation
Summary
The EVAC module features 4 monitored control outputs for alarm devices. The
outputs can be activated either manually or automatically via fire detection control
unit. When automatically activated, one or more control outputs can be allocated to
each detector zone. The allocation is made in programming step 31. The control
outputs are manually activated via operating panel.
Note:
The control lines have to be closed with EOL FCE1002.
Ref Setting / Function
CN4 OFF = Buzzer disabled
ON = Buzzer enabled (has to be ON)
F1 Fuse 500 mA T EVAC-1
F2 Fuse 500 mA T EVAC-2
F3 Fuse 500 mA T EVAC-3
F4 Fuse 500 mA T EVAC-4