User Manual

Installation
13
Building Technologies A6V10265083_b_en_NL
Fire Safety & Security Products 04.2010
4.2 Mounting
6
2
1
5
4
3
Procedure
1. Remove front cover
2. Determine mounting location (not behind a door)
3. Mark position of mounting screws (use enclosed drilling template) and drill holes.
Installation accessories not included in cabinet:
screws min. 4x50mm
plastic dowels
c-shaped washers or lock washers
4. Mount chassis, if required with distance sleeves (1)
5. Break out cable entries (3) and mount cable glands (PG11) if required (2)
6. Insert inscription stripes (4)
Templates for inscription stripes are available as Word files at the hotline.
7. Remove the recess (5) if optional key switch is used
8. Insert batterie right (6)
9. Place the mid positioning battery holder
10. Connect all periphery devices (refer to page 14 – 19)
11. Put the secon
d battery holder on the left and screw it to lock both batteries
12. Set jumpers on main board (refer to page 14)
13. Commi
ssion system (refer to page 29)
14. Adapt the user functio
ns where required (refer to page 31 – 42)
15. Mount front cover
Protect the mounted unit with its shipping carton during construction phase by using the shipping
carton