User Manual
d592d
19
Fire & Security Products
Siemens Building Technologies Group
06.2002
2.9.2 Einrichtungsüberwachung mit
Luftproben-Rauchmeldesystem
Luftproben-Rauchmeldesysteme in oder über den EDV-Geräten montiert gestatten ein
sehr gutes, selektives Überwachen der Einrichtungen. Die Absaugstellen werden direkt in
den Kühlluftstrom der zu überwachenden Geräte montiert. Durch den im Luftpro-
ben-Rauchmeldesystem eingebauten Ventilator werden kleinste Rauchmengen aktiv
durch das Rohrsystem direkt dem Melder zugeführt.
Für die Detailprojektierung sei an dieser Stelle auf die Richtlinien der einzelnen Systeme
verwiesen.
Luftprobeneinheit ASD-Mono
Absaugschläuche
APK = Luftprobeneinheit mit Rauchmelder
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
APK APK
Fig. 23 Einrichtungsüberwachung mit Luftprobeneinheit ASD-Mono
Merkmale:
- Platz für einen Ionisations- oder Streulicht-Rauchmelder
- Für Systeme mit kollektiver Adresse oder mit Einzelidentifikation
- Bis zu vier Absaugrohre anschliessbar (Länge je max. 20m)
- Elektronische Luftstromüberwachung
- Keine Löschansteuerung
- Kein Stromlosschalten der Einrichtung
- Feste Installation
Einsatz:
- Überwachung einzelner EDV-Geräte