F F FF
FRF
FR
FPK
Zuluft
A
M
≤40m
2
A
M
≤20m
2
belüftet
≤40m
2
unbelüftet
A
M
siehe Fig. 12
F = Ionisations-Rauchmelder
R = Streulicht-Rauchmelder
FPK = Luftprobeneinheit
A2400S = Sender des linearen Extinktions-Rauchmelders
A2400E = Empfänger des linearen Extinktions-Rauchmelders
A2400S
A2400E
Reflektor
≤0,30m2,10m - 3,50m
FPK
Rückluft
Fig. 11 Raumüberwachung für erhöhte Anforderungen
Die Überwachungsfläche der Raumüberwachung ist in Abhängigkeit des Luftwechsels pro
Stunde und der Raumhöhe zu wählen:
0 50 100 150 200
x/h
1
2
3
4
5
Anzahl Luftwechsel pro Stunde
6
7
h
Raumhöhe in m
B
C
A
Klassierung der Datenverarbeitungsanlagen
Klasse Überwachungsfläche A
M
pro punktförmigen Melder
Parallelabstände linearer
Extinktions-Rauchmelder
A max. 40m
2
max. 6,3m
B max. 25m
2
max. 5m
C max. 40m
2
max. 5m
Fig. 12 Diagramm zum Festlegen der Überwachungsmassnahmen