Specifications

External Accessories
Universal Test Kit (TS-31)
32
General Information
Universal Test Kit
Operating Instructions
A. Remove electrical loads from circuit breaker.
B. Plug TS-31 test set into a grounded 120V AC receptacle and
turn it on.The identifying turn-on message will appear:
C. Select appropriate ribbon cable assembly and connect it
between the TS-31 and the circuit breaker. Check alignment
and polarity. After pressing ENTER, the TS-31 will prompt:
D.Type in the catalog of the circuit breaker if a JD, LD, MD, ND,
PD Frame. If the unit being tested is a SB Encased Breaker,
type in the catalog number of the trip unit (located on the
side of the trip unit correct.)
After entering the catalog number information, press the
ENTER key. If an invalid catalog number has been entered,
the TS-31 will respond with:
and you will be asked to enter another catalog number.
E. If valid catalog number has been entered, the TS-31 will
prompt for breaker settings.The TS-31 will respond with:
For breakers with short time functions you will be asked:
For breakers with Instantaneous Pickup Setting:
For breakers with ground fault you will be asked:
In each case, enter your breaker’s switch settings. For exam-
ple, if your breaker is set for a continuous current of 70%,
type 70 and then press ENTER. Entry of erroneous data in the
above steps will result in false tests and results.
F. After entering breaker switch settings, you must select the
test you wish to have performed: The TS-1 will request:
Enter one of the following letters:
“L Long time or overload test
“S” Short time test
“I” Instantaneous test
“G” Ground fault test
“C” Current transformer continuity test
G. After entering the desired test, you will be prompted for the
phase to be tested.The TS-31 will display:
Enter one of the following letters:
A Phase A or Left Pole
“B” Phase B or Center Pole
“C” Phase C or Right Pole
“N” Neutral
H.The TS-31 will report the type of test you selected and give
you a chance to abort the test. For example, if “I” was
pressed above.The TS-31 will display.:
If you pressed the letter”A to abort, you will be given new
options (See Step K).
Safety Instructions
DANGER
Remove electrical loads from the circuit
breaker to be tested prior to performing
tests. Failure to do so can produce
erroneous results and possible electrical
malfunction.
Siemens Energy & Automation, Inc.
TS-31 Test Set. Press any key to continue.
Enter catalog number:
XXX...NOT found.
Press any key to continue.
Enter Continuous Current Setting in %:
Select Long Time Delay in Seconds:
Enter Short Time Pickup:
Enter Short Time Delay, 1-Fixed, 2-l
2
t:
Enter Short Time Delay in Seconds:
Enter Instantaneous Pickup Setting:
Select Ground Fault Type: 1-Residual,
2-Ground Return, 3-Unsure:
Enter Ground Fault Pickup Setting in %:
Enter Ground Fault Delay, 1-Fixed, 2-l
2
t:
Enter Ground Fault Delay in Seconds:
Enter test, L-Long, S-Short, I-Inst, G-Gnd Fault, C-CT,
Cont?
Enter phase to test:
Instantaneous Test
Press ENTER to Continue or A to Abort.
DANGER
Hazardous Voltage.Will cause death or serious
injury.
Turn off and lock out all power supplying the device
prior to cover(s) removal or while cover(s) are removed
and when installing any internal or external accessory.
Replace the cover(s) and shield(s) before power
supplying this device is turned on.