Specifications

Operations – Ground Fault Sensing Schemes
Ground Fault Sensing Scheme
18
The following are brief descriptions of the ground fault sensing
schemes as they relate to the Siemens Electronic Trip Unit.
Detailed technical and application information of the ground
fault sensing schemes is contained in NEMA Standard No.
PB 2.2 Application Guide for Ground Fault Protective Devices
for Equipment”.
Residual (3-Phase, 3-Wire): Under normal system conditions
(without ground fault), the vector sum of the phase currents
being monitored by the trip unit is zero.This is also true under
the condition of an overcurrent phase-to-phase fault and
phase-unbalance condition.When a phase-to-ground fault
occurs, the vector sum of the phase currents is directly
proportional to the magnitude of the fault.The trip unit’s
microprocessor uses this vector sum data in the execution
of the ground fault protection function.The trip unit utilizes
the internal breaker current transformers. No external current
transformers are required.
Residual (3-Phase, 4-Wire): In the 3-Phase, 4-Wire Residual
scheme a fourth current transformer is connected in the
neutral conductor to “Sensenormal neutral currents. Under
normal system conditions, the vector sum of the currents in
all phases equals the neutral current.This is also true under
the condition of an overcurrent phase-to-phase fault and
phase-unbalance condition.When a phase-to-ground fault
occurs, the fault current returns via a path other than the neu-
tral.Therefore, the vector sum of the phase currents no longer
equals the neutral current.This current differential is detected
by the trip unit and used in the execution of the ground fault
protection function.
Residual Sensing: Circuit BreakerWiring for Ground Protection
(3-Phase, 4-Wire System Shown)
Source Ground: In this scheme, the phase currents are not
used in detecting and processing ground faults.The trip unit
executes the ground fault protection function based on data
from a ground current sensor.This sensor is located on the
neutral connection to ground at the service entrance, and is
connected to the neutral transformer input terminals on the
trip unit.
Source Ground Current
Zero Sequence Ground Fault Protection